Electric actuators are key terminal devices in thermal power plant control systems, driving control and on-off valves. Brands differ significantly in terminal wiring, stroke commissioning and fault handling, yet the core workflow is highly consistent. This guide compiles the universal safety requirements and cable selection for electric actuator wiring, a commissioning comparison of seven mainstream brands (Rotork IQ, SIPOS 5/7, Limitorque MX/QX, AUMA SA/SAR, RAGA RA/RJ/RQM, SAI AI/MI, Xingli LT/LTQ), the universal commissioning workflow and precautions, and a common-fault quick reference. Brand-specific wiring and commissioning guides are linked at the end.
⚠️ Observe the following before any wiring or commissioning:
Cable selection:
| Cable type | Specification | Description |
|---|---|---|
| Power cable | 3×1.5–3×4.0 mm² | Sized to motor power; 380V three-phase or 220V single-phase |
| Control cable | 0.75–1.5 mm² | Digital/interlock signals; shielded cable |
| Analog cable | 1.0 mm² twisted pair, shielded | 4–20 mA command and feedback; run in its own conduit |
| Earthing cable | ≥2.5 mm² green-yellow | Protective earth, reliably bonded to the enclosure |
| Brand/Series | Commissioning tool | Password/entry | Seating mode | Distinctive features |
|---|---|---|---|---|
| Rotork IQ | Infrared setter | SET key | Travel or torque selectable | Non-intrusive, IP68 |
| SIPOS 5 PROFITRON | Panel keys + menu | PIN 9044 | Travel or torque selectable | VFD speed control + torque curve |
| Limitorque MX | Red/black panel buttons | Password 100 | Position/torque (open = position only) | Modutronic module |
| AUMA SA | Panel keys + adjuster shaft | Password 0000 | Travel + torque switches | Mechanical limit adjuster shaft A |
| RAGA | Panel keys + menu | SET key | Travel or torque selectable | H01–H10 menu system |
| SAI AI/MI | Panel keys + menu | Panel entry | Travel or torque selectable | Profibus-DP + HART |
| Xingli LT/LTQ | Panel + infrared + APP | Advanced setup password 9123 | Travel or torque selectable | Smart VFD + mobile APP |
| Fault | Universal checks | Remedy |
|---|---|---|
| Actuator does not move | 1. Supply voltage 2. ESD/interlock signals 3. Control signal 4. Fuses | Restore power; reset ESD; satisfy interlock; replace fuse |
| Motor rotates the wrong way | Jog and observe direction | Swap any two supply phases with power off |
| Valve will not close tight | 1. Close-torque setting 2. Valve seat faces 3. Packing tightness | Raise torque; lap seat faces; adjust packing gland |
| Motor thermal trip | 1. Torque setting 2. Valve sticking 3. Ambient temperature 4. Duty frequency | Adjust torque; free the valve; improve ventilation; reduce duty |
| 4–20 mA feedback deviation | 1. Potentiometer/encoder 2. Cable shielding 3. Recalibrate | Replace potentiometer; check shield earthing; recalibrate 4 mA and 20 mA |
| No response to remote control | 1. Local/remote switch 2. Control wiring 3. DCS output 4. Communication parameters | Switch to remote; repair broken wire; check DCS channel; verify comms parameters |
| Limit switch does not actuate | 1. Cam position 2. Travel switch 3. Wiring | Reposition cam; replace travel switch; repair wiring |
| Actuator hunting/oscillation | 1. Dead-band setting 2. PID parameters 3. Signal interference | Increase dead band; tune PID; improve signal shielding |