The LT/LTQ series from Shanghai Huali (Xingli) Fluid Control are smart variable-frequency electric actuators combining intelligent and VFD control with adjustable motor torque and speed: LT is multi-turn and LTQ is part-turn, with non-intrusive infrared commissioning and mobile APP support. Reference: Xingli LT/LTQ smart VFD electric actuator installation and commissioning manual.
LT/LTQ comes in three wiring variants by control type — on-off, on-off with feedback, and modulating. Main terminals:
| Terminal | Function | Description |
|---|---|---|
| Three-phase supply | 3×380V AC | Three-phase supply (LT multi-turn) |
| Single-phase supply | 1×220V AC | Single-phase supply (small actuators) |
| PE | Earth | Protective earth terminal |
| Open/close/stop | Remote digital control | Remote open, close and stop inputs |
| Analog command | 4–20 mA DC input | Modulating: DCS/PLC analog command |
| Analog feedback | 4–20 mA DC output | Position feedback output |
| Relay feedback | 8-relay output | Contact functions freely configurable (open, close, alarm etc.) |
| Communication | RS485 / Modbus RTU | Optional fieldbus interface |
Wiring notes:
| Key | Main function | Auxiliary function |
|---|---|---|
| ESC(Local/OFF/Remote) | Mode key: local/stop/remote | Back: one menu level up |
| SET(Stop) | Stop key: stops the actuator | Confirm: confirm/save in menus |
| ▼ | Close key: local closing | Down/decrement |
| ▲ | Open key: local opening | Up/increment |
Three operating modes:
Note: all parameter setting must be done in inhibit mode; queries only in remote or inhibit mode. After power-up the actuator restores its pre-outage mode.
Basic settings has three sub-items — close setting, open setting, travel setting:
Note: if the encoder count reaches its ceiling (4-stage: 131072; 5-stage: 1048576) before the valve reaches full open/close, the required output turns exceed the factory range — consult the manufacturer.
| Parameter | Description |
|---|---|
| Supply type | "AC-380" three-phase; "AC-220" single-phase |
| Closing direction | "clockwise" or "counter-clockwise" |
| Opening torque | Percentage of rated (40%–120%) |
| Closing torque | Percentage of rated (40%–120%) |
| Remote control type | Digital or analog |
| Control signal type | "self-holding" or "jog" |
| Dead band | Default 20‰, adjust as needed |
| Command calibration | Calibrate 4 mA and 20 mA command values |
| Feedback calibration | Calibrate 4 mA and 20 mA feedback values |
| Relay configuration | Define the 8 relay contact functions (position/alarm etc.) |
| Fault | Possible cause | Remedy |
|---|---|---|
| Remote control fails | Supply abnormal; comms parameters mismatch; oxidized/loose terminals | Check terminal voltage; verify station address/baud/parity; clean terminals |
| Encoder counts frozen | Encoder connection loose | Re-seat the encoder cable |
| No action after setting | Travel setting beyond mechanical limit | Check the travel setting against mechanical limits |
| Modulating overshoot | Inertia zone too small; micro-pulse time too long | Increase inertia zone; decrease micro-pulse time |
| Relay output abnormal | Wrong contact function/type configuration | Reconfigure relay functions and types |
| Comprehensive fault (OUT0) | See fault table | Consult the manual's fault table and act on the fault code |
Related reading: Universal Electric Actuator Wiring & Commissioning Guide; see also the Huali Xingli brand column.