The Rotork IQ series is a widely used non-intrusive smart electric actuator with IP68 protection. Commissioning is done via an infrared setter — no need to open the electrical compartment. Based on the IQ actuator manual (Publication E120C), this article covers terminal wiring for the on-off and modulating versions, travel/torque limit setting, and common fault remedies.
| Terminal | Function | Description |
|---|---|---|
| 1、2、3 | Three-phase supply L1、L2、L3 | 380VAC, phase order irrelevant |
| E | Earth terminal | Protective earth, must be reliably connected |
| 4(-)、5(+) | 24V DC control power | Internal regulated output for external control circuits |
| 5、33 | Close command input (CLOSE) | Remote close signal, to DCS/PLC DO card |
| 5、34 | Remote stop/hold | Remote stop signal |
| 5、35 | Open command input (OPEN) | Remote open signal, to DCS/PLC DO card |
| 6、7 | Valve fully-closed feedback | Passive closed-limit contact, to DCS/PLC DI card |
| 8、9 | Valve fully-open feedback | Passive open-limit contact, to DCS/PLC DI card |
| 42、43 | Fault feedback | Fault signal |
| 10、11 | Remote-control signal | Remote signal |
Wiring notes: for on-off valves, jumper internal supply 4 to 36; jumper 5 to 34 for pulse signals, no jumper for maintained signals.
| Terminal | Function | Description |
|---|---|---|
| 1、2、3 | Three-phase supply L1、L2、L3 | 380VAC, automatic phase recognition |
| E | Earth terminal | Protective earth, must be reliably connected |
| 26 | Analog command input + | Remote control signal, to DCS/PLC AO card |
| 27 | Analog command input - | Remote control signal, to DCS/PLC AO card |
| 22 | Analog position feedback + | Analog position feedback, to DCS/PLC AI card |
| 23 | Analog position feedback - | Analog position feedback, to DCS/PLC AI card |
Wiring notes: for modulating valves, jumper 4 to 41 and 5 to 39.
| Fault | Possible cause | Remedy |
|---|---|---|
| Actuator does not move | Phase loss; ESD not reset; interlock not satisfied | Check three-phase supply; reset ESD; check interlock circuit |
| Will not close / not tight | Close torque set too low; valve sticking | Increase torque appropriately; check valve mechanically |
| Thermal trip | Motor overload; high ambient temperature | Check torque setting; improve ventilation |
| Feedback deviation | Potentiometer or encoder position shifted | Re-set travel limits and recalibrate 4–20 mA output |
Related reading: Universal Electric Actuator Wiring & Commissioning Guide; see also the Rotork brand column.