The AUMA SA series is the multi-turn electric actuator from Germany's AUMA; the SAR series is the part-turn (quarter-turn) version. Both use non-intrusive commissioning — all parameters are set from the control panel keys. Based on the AUMA SA multi-turn actuator manual, this article covers on-off terminal wiring, a six-step commissioning procedure and common fault remedies.
| Terminal | Function | Description |
|---|---|---|
| L1、L2、L3、PE | Three-phase supply + earth | 380V three-phase |
| 2、11 | Remote close command | Internally powered, remote dry contact |
| 3、11 | Remote open command | Internally powered, remote dry contact |
| 6、7 | Valve fully closed | Position feedback, dry contact |
| 6、8 | Valve fully open | Position feedback, dry contact |
| 6、10 | Remote signal | Remote signal |
Close limit:
Open limit:
| Fault | Possible cause | Remedy |
|---|---|---|
| Cannot enter menu | Wrong password; not in local mode | Verify password 0000; switch to local mode |
| Limit switch does not actuate | Adjuster shaft A wrongly positioned | Readjust the limit cam position |
| Motor thermal trip | Excessive torque; frequent starts | Check valve mechanically; reduce duty frequency |
| Feedback drift | Ageing or loose potentiometer | Replace potentiometer; recalibrate 4–20 mA |