SIPOS electric actuators come in two classes: ECOTRON (economy, contactor-controlled, fixed speed) and PROFITRON (professional, VFD-controlled, variable speed with torque curves). The SIPOS 7 series is the successor to series 5, sharing the same architecture and operating philosophy. This article covers terminal wiring for both classes, commissioning procedures and common fault remedies. Reference: SIPOS 5 Flash ECOTRON/PROFITRON Chinese manuals (E20185-P920-B701-X-5D00), PROFITRON wiring diagram (Y070.061/CN), SIPOS SEVEN manuals (Y070.301/ZH, Y070.302/ZH).
| Terminal | Function | Description |
|---|---|---|
| U1、V1、W1、PE | Three-phase supply + earth | 380V three-phase input (phase order irrelevant) |
| X3.1-3、X3.1-6 | Stop command | Valve stop signal |
| X3.1-3、X3.1-4 | Close command | Remote close signal |
| X3.1-3、X3.1-5 | Open command | Remote open signal |
| X3.2-1、X3.2-2 | Fully-open feedback | Open feedback signal |
| X3.2-5、X3.2-6 | Fully-closed feedback | Closed feedback signal |
| X3.2-11、X3.2-12 | Fault signal | Fault feedback signal |
Wiring note: terminals 18 and 19 must be jumpered.
| Terminal | Function | Description |
|---|---|---|
| U1、V1、W1、PE | Three-phase supply + earth | 380V three-phase input (phase order irrelevant) |
| X3.2-14(+) | Command input + | Control command positive |
| X3.2-15(-) | Command input - | Control command negative |
| X3.1-1、X3.1-2 | Position feedback | 4–20 mA position feedback (+/-) |
| X3.2-13、X3.2-14 | Remote control | Remote signal |
Wiring note: position feedback needs no DCS card power supply.
| Fault code/symptom | Meaning | Remedy |
|---|---|---|
| ESD alarm | Emergency shutdown triggered | Check ESD source, clear the fault, reset |
| Phase-loss alarm | Three-phase supply loss | Check supply lines and fuses |
| Torque exceeded | Valve sticking or packing too tight | Check valve mechanically; adjust torque setting |
| Travel exceeded | End positions wrongly set | Readjust end positions |
| VFD fault | Overcurrent/overvoltage/overheat (professional) | Check load; improve cooling; replace VFD if necessary |
SIPOS 7 (SEVEN ECOTRON/PROFITRON) inherits the series 5 VFD architecture and commissioning philosophy, upgrading the HMI, diagnostics and fieldbus communication — adding a Web server, richer condition monitoring and predictive maintenance. Terminal wiring is essentially identical to series 5; commissioning uses a graphical interface.