Field commissioning procedure for boiler damper and swinging-burner pneumatic control systems built on cylinders with DE/3M, SA/CL or TZID-C positioners (including circuits with triple-failure protection). Two parts: pre-commissioning checks (11 items covering air piping, cleanliness, purging, waterproofing and mechanical installation) and system commissioning (air-pressure setting, mechanical and electrical checks for cylinders with conventional positioners, and the setup of cylinders with TZID-C smart positioners) — each step with its tolerance and the corrective path.
This procedure applies to damper control systems built on cylinders fitted with DE/3M, SA/CL or TZID-C positioners. Field service personnel must follow it strictly.
1. Before pressurizing the actuator, verify that the working-air line, control-signal air line and protection-signal air line (the latter only on circuits with triple-failure protection) are correctly installed.
2. For actuators supplied with air locally (including TZID-C smart positioners), check that a shut-off valve and a filter-regulator are correctly installed at the air inlet to ensure air cleanliness.
3. Check the working air quality against instrument-air standards; if it fails the technical requirement, raise it with the owner promptly and record it truthfully in the service report.
4. Ask the installation contractor about the purging of all air lines; never allow a line to be commissioned without purging.
5. Ensure the air-signal output fittings of the control cabinet (box) connect to the tubing without leakage — leaks seriously degrade commissioning.
6. For actuators installed where water ingress is possible, require the contractor or owner to waterproof the cable-gland holes or reorient the electrical equipment, preventing water damage. Record this item in the service report.
7. Check every actuator's installation. If the feedback linkage plate could strike the damper crank during cylinder motion, require the contractor to reorient the cylinder (rotate 90°) to avoid damage.
8. For cylinders of bore 160 and above, check that the cylinder output shaft is perpendicular to the damper center shaft and the cylinder base, and that the output-shaft axis lies in the plane of the damper crank's motion curve — otherwise the two will fight and damage the equipment.
9. When connecting the actuator to a swinging-burner damper, instruct the contractor on the method: first pull the cylinder output shaft out to half stroke (loosen the air-lock bypass screw and retighten it only after the cylinder and damper are joined), set the damper to mid-zero on the dial, then join the two through the U-clamp.
10. Check that all U-clamp locknuts are tightened — essential for repeatable linear output.
11. Check that the flexible-metal fittings of every actuator signal line are leak-free — essential for repeatable linear output and range compliance.
2.1 Air-pressure setting
1.1 After confirming the cabinet supply line is purged clean, open the cabinet air switch and set the supply pressure with the regulator to the value on the cabinet nameplate.
1.2 Open the cylinder working-air valve and set the filter-regulator output to 0.5 MPa. When commissioning swinging-burner cylinders, first set the pressure to 0.35 MPa to protect the equipment from mechanical binding or other problems, then raise it to 0.5 MPa once commissioning is satisfactory. For cylinders with a smart positioner, set 0.5 MPa.
2.2 Mechanical commissioning — cylinder with conventional positioner
2.1 For one-to-one circuits, command the electro-pneumatic converter to 10% and 90% via the DCS or a signal generator, and check whether the cylinder output shaft travels 10% and 90% of full stroke accordingly. With the positioner healthy: error below 10% is normally removed by trimming the converter output; error between 10% and 20% is removed by adjusting the cylinder feedback spring and zero screw; error above 20% points to air-line leakage.
2.2 For one-to-two or one-to-four circuits, command 10% and 90% and check that all cylinders under that converter travel identically and correctly. If their travels differ, mechanically adjust all cylinders to within 10% error (all positive or all negative), then trim the converter output to remove the residual error; error above 20% is handled as above.
2.3 After zero and span are set, verify errors at 0%, 25%, 50%, 75% and 100% — the output-shaft travel must be linear, which is essential for the electrical commissioning that follows. Cylinder accuracy must reach class 1.5.
2.4 For cylinders with SA/CL positioners: if the span error is within 15% of the standard value, meet the range requirement with the zero screw and converter output — avoid moving the span screw, since on site it is hard to keep the output travel linear afterwards; if the span error exceeds 15%, look for air-line leakage.
2.5 Throughout cylinder commissioning, check that damper opening is linear with the cylinder. If the damper has a mechanical fault, or the cylinder mounting (including the damper crank) is wrong, resolve it with the owner or contractor. If a damper or mounting problem prevents full-stroke output, do not casually shift the cylinder's standard stroke via the control signal — it severely distorts the feedback-current linearity. The best fix is to change the damper crank dimensions.
2.3 Electrical commissioning — cylinder with conventional positioner
3.1 Open the position transmitter cover and check the feedback wiring and loop under load with a DC voltmeter: normally 20–24 V; if below 18 V, check for earth faults or a damaged DCS output card.
3.2 Command the cylinder to 50% output and check that the transmitter crank is perpendicular to the cylinder (DE/3M positioner) or parallel (SA/CL positioner) — essential for linear feedback current.
3.3 At 50% output, adjust the transmitter's eccentric wheel so its index line aligns with the triangular mark on the circuit board; then verify the locknut is tight — essential for repeatable linear feedback.
3.4 Set the direct/reverse switch of the feedback current per the DCS requirements: cylinder closed = 4 mA and cylinder open = 20 mA is direct action; the opposite is reverse. For DE/3M positioners set the transmitter angle switch to 90°; for SA/CL positioners set it to 65°.
3.5 Command 0 and 100% and trim the transmitter zero and span potentiometers for 4 mA and 20 mA; then check 25%, 50% and 75% — each point's error must be below 2%.
3.6 After commissioning the transmitter, secure the leads inside it to prevent loosened or damaged connectors from cable strain.
2.4 Commissioning — cylinder with TZID-C positioner
4.1 Open the positioner cover and measure under load with a DC voltmeter: input terminals 11+/12− and feedback output terminals 31+/32−. Input voltage is normally about 8.7 V; feedback side 18–24 V.
4.2 Open the working air at 0.5 MPa (0.35 MPa initially for swinging-burner cylinders), enter operating mode 1.3 from the keypad, stroke the cylinder fully open and closed by hand and confirm the mechanical parts (including the damper) are sound before proceeding (note: restore the swinging-burner supply to 0.5 MPa afterwards).
4.3 Enter parameter menu P1.1 to start auto-tuning. After it completes, check that the cylinder action direction, local display and position indication (feedback current) match the DCS requirements; if not, satisfy the control system by changing P2.3, P3.2 and P8.2 (see the TZID-C installation and operating manual for details).
4.4 Position-display errors at all points must be below 1%; otherwise trim the zero and span potentiometers on the positioner feedback board.
4.5 When all commissioning is complete, set the operating mode to 1.1 (fixed control mode), refit and screw down the positioner cover.