Electric & pneumatic actuators, dampers and heaters — resources, guides and global supply actuators@163.com WhatsApp: 13853147838 中 EN
Request a Quote

Bernard Controls AT Range Multi-Turn Actuators: 7–500 N·m, BC App Setup, IP68

source:original    date:2026-11-10

The Bernard Controls AT range of multi-turn electric actuators: the "essentials" series for conventional valve automation — seven models from 7 to 500 N·m, S4 duty on every model, IP68, and parameterisation from a phone via the BC App. A generation-mate of the heavy-duty full-feature BT range, AT takes a "select the essentials" approach for a competitive yet performing light-duty product, in FLAT (on-off) and LOGIC (modulating) versions. The brochures are already online in our Bernard Controls library; this article collects the selection essentials.

1. Model range and torque steps

ModelOutput torque (N·m)
AT312–30
AT6L24–60
AT624–60
AT77–70
AT1456–140
AT25100–250
AT50200–500

Direct-mount output 7–500 N·m (go to the BT range for higher torque); a wide choice of output speeds; SWITCH and LOGIC versions, the modulating one rated Class III for higher duty performance.

2. Feature set

FeatureDetails
BC App smartphone setupBluetooth configuration and operation from a phone: position settings, alarm descriptions, troubleshooting guides, documentation, Bernard Controls Assistance; the full configuration uploads in one step — complex settings made simple
Declutch-free handwheelMotor priority, no clutch operation; foldable handle
Wide stem acceptanceRemovable screw cap suits rising-stem valves; watertight stem-cover fixation
Local commandsTwo buttons plus a padlockable selector — clear, reliable local open/close/stop
Heavy-duty designFull aluminium enclosure with durable powder coating (grey/champagne); IP68; anti-condensation heater, travel and torque switches standard
Two cover positionsOptional cover orientation for different mounting directions

3. AT or BT?

AT = "The essentials": conventional small-to-mid-torque valve automation, everything needed at a competitive price. BT = "The complete solution": 12/30–500 N·m, C4 corrosion protection, full LOGIC control. Rule of thumb: AT for standard water/HVAC/general-industry valves; BT where corrosion protection and control complexity are higher. Both brochures are downloadable from the library article for side-by-side comparison.

Related reading

Bernard Controls library, 70 files (AT/BT brochures EN/CN) · Bernard-derived library, 27 files · Bernard full-series atlas · Actuator braking methods

For Bernard (incl. Beijing) sizing and alternatives submit an RFQ.

Source: Bernard Controls brochure_AT_ENG_GRP_rev04a (downloadable on this site); compiled by actuators.cn.

An industry resource for electric & pneumatic actuators, dampers and heaters: brand manuals, sizing guides and maintenance know-how. Global brands in, China manufacturing out.