What Do Ruiji RJ Intelligent Actuator Alarm Codes F-05 to F-15 Mean?

source:    date:2026-10-04

When the alarm zone of a Ruiji RJ intelligent electric actuator shows a F-05 to F-15 code, match it against four groups: signal alarms (F-05 lost 4-20mA signal, F-06 simultaneous open/close signals, F-13 phase loss), ESD alarms (F-08 closing, F-09 opening, F-10 ESD signal still present), torque alarms (F-11 closing over-torque, F-12 opening over-torque), and position alarms (F-07 internal position error, F-14/F-15 no position change detected while closing/opening). Over-torque alarms clear by moving a short distance in the opposite direction, resetting the torque value, or re-powering; "no position change" alarms set a direction inhibit that must be cleared by reset. The full code table and the RJ wiring diagram are below.

Ruiji RJ intelligent actuator wiring diagram: power lines I-III and terminal functions 1-25

Ruiji RJ actuator wiring diagram: terminals 1-8 and 17-25 are standard functions, 9-16 are optional (specified at order)

1. Alarm code table (F-05 to F-15)

CodeMeaningActuator responseClearing
F-054-20mA control signal lostActs per item 7 "signal-loss action" of the working settings; monitor relay de-energizedRestore signal
F-06Remote open and close signals present simultaneouslyMotor stoppedCorrect signal
F-07Internal error detected by position sensingMotor stoppedAuto-resets after about 1 second
F-08ESD close operation in progress——
F-09ESD open operation in progress——
F-10ESD control signal still presentAll other electrical operation (local or remote) ineffectiveWithdraw the ESD signal
F-11Closing torque exceeded setting (close over-torque)Motor stopped; flag set inhibiting closing directionMove a short distance toward open / reset close torque setting / re-power
F-12Opening torque exceeded setting (open over-torque)Motor stopped; flag set inhibiting opening directionMove a short distance toward close / reset open torque setting / re-power
F-13Phase loss detected via position sensingMotor stoppedRestore three-phase supply
F-14No position change detected while closing (blockage / electric clutch not engaged / position potentiometer faulty)Motor stopped; monitor relay de-energized; closing direction inhibitedReset to clear the inhibit
F-15No position change detected while opening (blockage / electric clutch not engaged / position potentiometer faulty)Motor stopped; monitor relay de-energized; opening direction inhibitedReset to clear the inhibit

2. How to read the four alarm groups

2.1 Signal alarms (F-05/F-06/F-13): check external signals first

F-05 (lost signal) is the most common: when the 4-20mA command signal is lost, the actuator does not simply stop — it moves according to the preset "signal-loss action" (item 7 of the working settings), while the monitor relay drops out to tell the control system. F-06 means remote open and close commands arrive together, pointing to a miswired or disturbed signal loop. F-13 is phase loss detected through the position sensor, stopping the motor to protect it.

2.2 ESD alarms (F-08/F-09/F-10): safety interlock comes first

F-08 and F-09 are status indications — an ESD close/open stroke is in progress — not faults. F-10 deserves attention: as long as the ESD signal remains, any other electrical operation, local or remote, is ineffective. This is intentional safety interlocking; withdraw the ESD signal before attempting any other operation.

2.3 Torque alarms (F-11/F-12): three ways to clear

After an over-torque trip the motor stops and a direction-inhibit flag is set. Any one of three actions clears it: move a short distance in the opposite direction; re-set the over-torque protection value for that direction; or re-power the actuator. If over-torque recurs frequently, check for a jammed valve or a torque setting set too low — do not just reset and force it.

2.4 Position alarms (F-07/F-14/F-15): mechanical and potentiometer causes

F-07 is an internal position-sensing error that auto-resets after about one second — occasional occurrences can be observed; frequent ones warrant checking the position feedback circuit. F-14/F-15 ("running but no position change") points to three possibilities: a blocked valve, the electric clutch not engaged (manual/electric changeover incomplete), or a faulty position potentiometer. After ruling out mechanical causes, check the potentiometer and counting mechanism. These alarms also de-energize the monitor relay and inhibit the affected direction until reset.

Summary

  • Four groups: signal (F-05/06/13), ESD (F-08/09/10), torque (F-11/12), position (F-07/14/15) — first tell status indications from protective trips;
  • Two safety behaviors: with F-10 the ESD signal blocks all electrical operation; with F-05 the actuator carries out its preset signal-loss action automatically;
  • Two clearing rules: over-torque (F-11/12) clears by back-off, re-set or re-power; "no position change" (F-14/15) requires a reset before the direction works again.

Need Ruiji RJ/RQM series intelligent actuators sized, quoted, or spare parts? Submit an RFQ.