An AUMA valve at one plant behaved strangely: operations reported "not fully closed"; local inspection found the closing-torque trip. After reset, the DCS close command closed the valve normally — but the moment it reached the closed limit, the valve opened by itself. The DCS had issued no open command, the interposing relay had not operated, the cable checked out, and a small amount of water was found inside the terminal strip; after drying, the fault persisted. This article compiles the troubleshooting approach and a parallel case.
Bottom line: an AUMA motor-operated valve reopens the moment it reaches closed, while the DCS issued no open command, no relay operated, the cabling tests sound, and drying the wet terminals changed nothing — prime suspect: the open-command circuit is being made without a command (damp conduit cabling / tracking), next a welded open-command relay contact. Water ingress is the most common root cause of “valve operates itself” events; “we dried it” is not the same as “the circuit is dry”.
"Reverses at limit" with no open command: focus on whether the open circuit is being bridged without a command:
| Check point | Method | What it tells you |
|---|---|---|
| Open-command circuit insulation | Megger the open-command cores to earth and between cores | Dampness may remain inside the conduit even after the terminal box was dried — falling insulation leaves the open circuit “half-made” |
| Relay contacts | Inspect the DCS-side open-command relay contacts | A welded contact keeps the loop made after the DCS command is withdrawn |
| Actuator terminals & plugs | Open the junction box; look for tracking marks and water films between open/close terminals | Moisture inside AUMA internal plugs can also cross-talk channels |
| Cross-brand evidence | A Rotork normally-open MOV that “closed itself” at another plant | Water in the terminals; dried and re-sealed, fault cleared — command-circuit wetting is the common root of self-operation |
| Internal control board | Swap the board once the above are cleared | Check the open-direction thyristor/relay output channel |