The Rotork IQ series is one of the most widely used intelligent electric actuators in power plants. This reference, compiled from the long-term field experience of power-plant maintenance technicians, breaks 28 common faults into five quick-reference tables in a “symptom → likely cause → check & fix” format, covering valve stem output, limits, position indication, modulation hunting, power supply, and display/alarm — find the symptom, then work through the fix column step by step.
Note before use: menu items and terminal numbers may differ between batches and firmware versions; always confirm against the manual of the specific unit, and when replacing boards, save the device parameters first.
Field reminder: before replacing any board, record the unit parameters with the setting tool and restore them afterwards before judging the fault — limit, dead-band and torque settings are lost when main power fails while the backup battery is dead (items 2 and 14).
Manual first, then electric, then disconnect the valve — in that order, rule out a stuck clutch, a failed motor and a jammed valve (steps A→D of item 1).
| Table 1 Mechanical & motor faults (5 items) | |||
|---|---|---|---|
| # | Symptom | Likely cause | Check & fix |
| 1 | Valve stem has no output | Hand/auto clutch stuck in manual (motor spins idle); motor not turning; jammed valve; sleeve seized, stripped or loose | Check manual operation first, then whether the motor turns; if neither works, disconnect the valve coupling and inspect the sleeve |
| 6 | No action in remote or local, or motor turns one way only without limiting | Hand/auto clutch stuck; burned motor; wrong power wiring or unbalanced three-phase supply | Inspect clutch and motor; verify power wiring and phase balance |
| 7 | No action in remote or local; motor winding, thermal protection or electromagnetic feedback reads open | Motor burned out | Replace the motor |
| 13 | Manual works, but it will not switch to electric | Clutch retaining spring stuck in the manual direction | Remove the hand wheel, release the spring, reassemble |
| 18 | Setting and motion normal, but it cannot pass a certain position | Valve sticking; gear-reducer mechanical limit set backwards | Check manually and re-set the mechanical limit |
Position-indication and feedback fixes concentrate on two boards: the counter board (items 3-4) and the (servo) position feedback board (items 4, 15, 24, 25).
| Table 2 Limits, position display & feedback (8 items) | |||
|---|---|---|---|
| # | Symptom | Likely cause | Check & fix |
| 2 | Cannot hold the set travel position at full open/close; stem slams into the valve body | “Close/open limit LC/LO” parameter lost | Re-set the limits, or change the parameter from “torque open/close” to “limit open/close” |
| 3 | Displayed position disagrees with actual position; drifts again after re-setting limits | Counter board failure | Replace the counter board |
| 4 | Actuator runs but shows no position | Counter round magnet or counter board failed; if terminals 22/23 deliver no 4-20 mA, the (servo) position feedback board is suspect | Check the counter magnet and board; measure 22/23 current and replace the feedback board if needed |
| 15 | Motion normal but no position feedback (22/23 loop delivers only 1-3 mA) | Position feedback board fault; or external feedback cable fault | If re-setting does not help, replace the feedback board; if the signal recovers when the loop is disconnected, the external cable is faulty — replace it |
| 17 | Valve will not fully close; still fails after re-setting the travel limit | Valve damaged | Repair or replace the valve |
| 20 | In hand/auto, displayed position and feedback both frozen; “limit open/close LO/LC” cannot be set | Main board dead | Replace the main board |
| 24 | Remote dead, local works, but displayed position does not change | Loose connector; if re-seating does not restore remote, the feedback board is faulty | Re-seat the connectors; if everything else is normal yet remote still fails, replace the position feedback board |
| 25 | Local normal; remote cannot close; in remote open it runs to full open regardless of signal | Position feedback board fault | Re-setting limits does not help — replace the (servo) position feedback board |
For hunting, adjust the dead-band first; for torque trips, check lubrication and the valve first — the checking order given by the original field table.
| Table 3 Modulation & torque faults (4 items) | |||
|---|---|---|---|
| # | Symptom | Likely cause | Check & fix |
| 5 | Hunting up and down in remote modulation without settling | Dead-band parameter Fd too small; position feedback board fault | Increase Fd; if hunting only stops above Fd = 20, replace the feedback board; if it persists after replacement, fit a lower-speed motor or enlarge the thread pitch between sleeve and stem |
| 12 | Normal unloaded; under load closing stops around 40% (close torque set to 99; hand wheel closes fully; closed fully when new but not after some service) | Actuator undersized | Step up one actuator size |
| 16 | Torque protection trips during motion and persists even with increased torque settings | Actuator grease dried out; valve jammed | Check actuator lubrication and valve condition |
| 19 | Motor vibrates during motion, starts and stops, runs slow | (Solid-state) relay fault (with the hand/auto clutch cleared) | Replace the solid-state relay and re-check |
Follow two lines: breaker trips → relay control board / motor windings; fuse blows → transformer. A dark backlight starts at the fuse and connectors.
| Table 4 Power supply, fuse & battery faults (5 items) | |||
|---|---|---|---|
| # | Symptom | Likely cause | Check & fix |
| 9 | Supply breaker trips the moment three-phase power is applied | Relay control board fault; burned motor windings | Check the relay control board and motor windings |
| 10 | Fuse blows at supply voltage above 400 V and again after replacement | With the power board silicon rectifier normal, the transformer primary resistance is too low | Replace the power board assembly or the power transformer |
| 11 | Backlight dark with three-phase supply normal | Actuator fuse blown; main board power connector loose | Check the fuse and re-seat the main board power connector |
| 14 | No action in remote or local; open/close limit LEDs flashing | Battery voltage low — parameters lost during a main-power outage | Replace the battery and re-set the parameters |
| 21 | After fitting a new power board, its silicon rectifier heats up rapidly at power-on | Components on the main board burned | Replace the main board |
Erratic alarms and LED anomalies are mostly main-board related; the IQ MK2 torque sensor fault has its own signature (item 26).
| Table 5 Board & alarm-signal faults (6 items) | |||
|---|---|---|---|
| # | Symptom | Likely cause | Check & fix |
| 8 | No action in remote or local; setting tool shows “H1 torque switch tripped” and “H6 no electromagnetic feedback” | (Solid-state) relay has no output | Replace the relay control board or the power board assembly |
| 22 | No action in remote or local; accepts no setting signal; position displays in manual | Main board and relay control board fault; or the switch magnet broken/missing | Replace the main board and relay control board; inspect the switch magnet |
| 23 | Remote normal; selecting local immediately raises “actuator alarm” | Local control board fault | Replace the local control board |
| 26 | A new IQ MK2 shows the “valve alarm” symbol, clearable manually; in local forward/reverse the relay trips immediately | Torque sensor fault | Open the motor and replace the torque sensor |
| 27 | Backlight dark, garbled symbols, or all three status LEDs lit together | Main board fault; if the run LED and open/close limit LEDs light together, the limit setting contradicts the valve rotation direction | Replace the main board; re-set the direction contradiction |
| 28 | Some alarm contacts will not change over; remote/local status cannot be detected | Main board or input/output processing board fault | Replace the main board or the I/O processing board |
Beyond the tables, many faults stem from improper installation, setting, or operation, and several often appear mixed together — analyze them one by one with the “alarm display” and the “H help display.”