Common Electric Actuator Faults and Answers: 15 Cases with Causes and Remedies
source:    date:2026-10-01

Fifteen of the most common field faults of valve electric actuators, with causes and remedies, for quick reference by maintenance staff.

Common actuator faults and remedies
FaultCauseRemedy
1. Motor will not startNo supply; low voltage; thermal relay (KH) tripped; T.SW tripped; valve operating torque too high.Check supply; check voltage; wait for KH to recover; 1. turn T.CW towards higher torque; 2. force-adjust; check the valve.
2. Motor stops during open/close travelOverload tripping the torque switch; thermal relay tripped; poor valve condition, high load.Raise torque setting if margin remains; adjust thermal relay; 1. check and restore the valve; 2. if possible, exercise the valve electrically periodically.
3. Gear limit switch will not stop motorMotor reversed; switch badly adjusted; adjusting screw not returned after setting; control supply switch faulty; limit-switch gear damaged.Rewire with valve at mid-position; readjust; return the adjusting screw; find and clear the fault; inspect/replace gear.
4. T.SW / GL.SW tripped but motor keeps runningMotor reversed; earth fault.Rewire with valve at mid-position; measure earthing resistance.
5. Open/close indicator lamps not litTorque switch tripped before the valve reached its position.Adjust the torque switch.
6. Remote opening indication frozenPotentiometer drive gear loose, potentiometer shaft not turning; poor supply; potentiometer failed.Tighten screws; check supply; replace potentiometer.
7. Motor runs but valve does not moveHand/electric changeover faulty; lock nut loose.Strip, inspect and repair; tighten nut.
8. Handwheel will not turnClutch dogs butting, not engaged.Rotate slightly to offset the dogs.
9. Stem vibrates at startStem nut loose or badly tightened.Remove stem cover or pipe plug and tighten the lock nut.
10. Poor insulationRain ingress (poor cable-entry sealing).Repair seals; dry components and motor; seal the cable entry.
11. Oil leakSeal damaged; high ambient pressure inside housing.Repair seals; loosen a non-critical screw (preferably the plug) to vent.
12. Local control OK, remote deadPLC input signal problem; EPC output problem; EPC burned.Check supply; check PLC input; check EPC output; replace EPC.
13. Local OK, remote position display lostRelay failed; connector fallen out; VOT transmitter burned.Check supply; check VOT output; check wiring; replace VOT.
14. No open/close action from the actuatorTorque switch failed; travel switch failed.Overhaul or replace torque/travel switches.
15. No hand/electric changeoverOverload tripped torque protection; lock hooks/gears damaged; disengaging lever fallen off the worm gear.Disconnect actuator from valve to reset torque; replace lock hooks/gears; refit lever.