EN  中
Limitorque Imported Actuator Commissioning Steps
source:    date:2026-10-01

Commissioning steps for imported electric actuators (as fitted to licensed units):

1. Tools: socket wrench, needle-nose pliers, voltage tester, multimeter, screwdrivers, watchmaker's screwdriver, special mini hex wrench.

2. Coarse feedback adjustment: de-energize the actuator and handwheel the valve to ~50% (observe the stem position); the 1 kΩ coaxial potentiometer output should read about 500 Ω — if not, loosen the potentiometer fixing screw and rotate it until the reading is correct.

3. Phase check: energize in local mode; press open/close then quickly stop; watch the motor rotation — if reversed, swap any two of L1/L2/L3.

4. Electric limit adjustment (close first, then open):

(1) Close limit: handwheel the valve fully closed (final confirmation by the piping crew); push in the middle clutch and rotate half a turn so the adjusting stem cannot spring out; rotate the screw marked CLOSE until the close limit switch actuates. If the valve is fully closed but the switch has not actuated, rotate the close-adjust screw with the closing direction until it presses the switch; if it actuates early, rotate against the closing direction until the valve is fully closed and the switch just actuates. Reset the clutch before adjusting the open limit.

(2) Open limit: same method as for the close limit.

(3) Rule of thumb: if a limit acts too late, rotate along the adjusting-screw direction; too early, against it.

5. Torque limit switches: open and close directions each have a dial — adjust the screws per the dial marking as required (torque switches protect against jammed-closed and seized valves; generally left as set).

6. Feedback signal: same as ordinary ZKJ-type actuator signal adjustment.

 
    
Support:Shandong Juxi Electromechanical Equipment Co.,Ltd.    Tel:+86-13853147838     Email:actuators@163.com    WhatsApp:13853147838/18678894019
© 2006-2025 Shandong Juxi Electromechanical Equipment