The DVC6200 is the upgraded successor to the Fisher DVC2000. Also HART-based, it supports full configuration, calibration and diagnostics via the 475 field communicator, and adds features such as an auto travel-calibration button and analog output activation. It suits all types of pneumatic control valves. This article organizes the complete DVC6200 commissioning workflow in five parts: 475 communicator calibration, guided setup (full initialization), feedback commissioning, auto-calibration button activation, and tuning.
Overview and Wiring
The DVC6200 is loop powered with 4–20 mA two-wire wiring, similar to the DVC2000: signal loop (IN+/IN-), position feedback output (separately supplied, 9–30 VDC) and limit switches (separately supplied, 4.3–30 VDC). HART communication connects through the signal loop.
Commissioning Procedure
Valve calibration with the 475 communicator
- Enter the interface and select HART
- Select Online, press Enter
- If an alert is present, select YES and press Enter
- From the Online menu select Configure, press Enter
- Select the Calibration menu, press Enter
- Select Auto Calibration
- At the warning select Out of Service
- Select CONTINUE, press Enter, then select Travel Control
- The valve auto-calibrates; wait without operating anything
- When calibration completes, confirm with OK
- Return to In Service — calibration is finished
Guided setup calibration (full initialization)
- Select HART → Online → Configure → Guided Setup
- Select Device Setup; at the warning select Out of Service
- Select pressure units (e.g. PSI)
- Select amplifier type: A or C for single/double acting; B for reverse-acting positioners
- Select Travel Control
- Select Fisher as the actuator manufacturer
- Select model and size from the actuator nameplate
- Choose valve fails open or closed per your conditions
- The positioner auto-detects the travel sensor direction
- Specify whether quick-exhaust and flow amplifiers are present
- Send the device setup data
- Accept factory defaults with YES
- Run the travel calibration: OK → YES
- After auto-calibration completes, restore In Service
Feedback commissioning (analog output activation)
- Configure → Manual Setup
- Change mode protection from In Service to Out of Service
- Select Outputs → Output Terminal
- Select Enable, press Enter
- Be sure to select Send to complete the setting
- Return the valve to In Service
Activating the auto travel-calibration button
- First set the valve to Out of Service
- Manual Setup → Instrument → Terminal Box
- Select Calibration Button, press the right key
- Select Autocal, press Enter
- Select Send to complete the setting
Tuning
- Manual Setup → Tuning → Travel Tuning
- Select Travel Tuning Set
- Use the up/down keys to choose C–M (C slowest, M fastest)
- Confirm the appropriate tuning
- Be sure to click Send
- Finally return the valve to In Service
Important: after all settings are complete the valve must be returned to In Service, otherwise remote control will not work.