SIPOS Power Boards Failing One After Another? Check for Internal Shorts First

source:    date:2026-09-26

A German SIPOS electric actuator (economy type) at one plant went completely dead: no power indication, no display at all. Inspection confirmed the power section (power board) had failed; after replacing the board (control board untouched), commissioning went perfectly — everyone thought the case was closed. Three days later, the newly replaced power board failed again.

What "replaced once, dead in three days" means

A single dead power board is routine: replace it. Two consecutive dead power boards almost certainly mean the root cause is not the board itself — the board is only the victim; something in the circuit keeps killing it. Peer analysis pointed in two directions:

1. A short circuit or ground fault near the power board: some point on the board shorted to ground or with degraded insulation, blowing each new board at power-up. The prime suspect is the installation environment: open the housing and look for foreign conductive objects — dropped copper strands, washers, burrs resting across live parts are the classic cause of "new board dies instantly";

2. Upstream stress on vulnerable components: peers noted that no-power-indication can also come from a failed thermal (sensing) resistor on the power board — and poor supply quality upstream (overvoltage, surges) can just as well kill board after board.

Checklist before installing the third board

After two consecutive failures, complete these steps before powering up again:

1. Inspect the interior for conductive debris and for burn/arc marks, especially around the power-board sockets and terminals;

2. Megger the power circuit to ground; confirm no short, no ground fault;

3. Check the supply quality: is the voltage high, any surge/lightning history, anything else sharing the same supply;

4. Check whether the control board was already damaged in the first failure (untouched in this case — damaged components on it can in turn drag down a new power board);

5. Only then power up, and watch the new board's temperature rise closely (a related case: an IQ-series actuator with a fresh power board showed the silicon rectifier block heating up rapidly — further inspection found burnt components on the main board, which had been taking the new board down with it).

Lessons

"A new board dies quickly" is the classic signature of a secondary fault: what is broken is not the board but its environment. The rule: when the same spot fails twice in a row, stop and ask why — do not simply replace again. Until debris, shorts/grounds, supply quality, and collateral board damage are ruled out, no third board should be installed.

 
    