Cost reduction is a principle always adhered to by SNNA. Each SQ actuator is integrated with an all-in-one frequency converter. This innovative concept is far superior to the traditional actuator solution of motor + reduction gear, which simplifies the mechanical structure and reduces manufacturing and application costs.
The basic control functions of the SQ control unit include motor power supply control, overload sensor control, solid-state reversing starter with mechanical/electrical self-locking function, and a monitoring control board that monitors all signals to ensure normal operation of the actuator.
The proportional control unit precisely modulates the valve opening proportionally according to analog signals. The valve position feedback unit converts the valve opening accurately into analog signals for feedback output.
All internal and external signals can indicate normal status or faults via LED indicator lights.
Frequency Conversion & Intelligence – Absolute Safety
Main power supply monitoring
Single-phase / phase loss protection
Wrong phase sequence connection protection
Motor overheating protection
Power / torque overload protection
Open/close fault relay
Frequency Conversion Intelligent Motor Control Unit
Equipped with comprehensive motor protection functions
Automatic correction of power supply phase sequence
No need for an external motor control cabinet
Optimize the control process by regulating motor speed
Wide adjustable range for closing torque and output shaft speed→ Greatly simplifies model selection in the initial design stage
Valve Protection Functions
Soft start and soft close
Output torque never exceeds the preset upper limit
Proportional Control Board
Input Signal:4-20mADC, 0-5VDC, 0-10VDC, 1-5VDC, 1-10VDC
Input Impedance: 250Ω
Potentiometer Signal: 500Ω–10kΩ
Excitation Signal: 2.3VDC
Dead Zone Adjustment: 0.1–4.5% adjustable (0.3% step, 15 steps in total)
Inhibit Time Adjustment: 0–7.5s (0.5s step, 15 steps in total)
Regulation Accuracy: 1%
Valve Position Transmitter
Input: 110/220VAC±10%Output: 4-20mA/1-10VDCFull Scale Adjustment: ±30%Zero Point Adjustment: ±20%
Monitoring Board
Overload and overheating protection
Fault and phase sequence error detection
Phase loss or power failure monitoring