Product: ONTRAC MME800 series intelligent modulating electric actuators
Overview: ABB's ONTRAC intelligent actuators lead the world in reliability and positioning accuracy. The ONTRAC MME800 modulating series positions in under 5 s, delivers high torque and adapts well, with excellent mechanical and motor control characteristics. Advanced microprocessor technology and communication interfaces connect to PC or DCS over standard HART or Profibus, accepting analogue or digital commands. Via the control panel the user configures parameters, functions, actuator actions and remote monitoring to match the valve's optimum control characteristics.
Main features:
Basic functions: 1. constant-torque V/F speed control; 2. electronic speed and torque setting; 3. configuration via digital communication or the local panel; 4. high-tech sensing makes commissioning extremely simple; 5. extensive monitoring and self-diagnostics.
| ONTRAC MME800 technical data | |
|---|---|
| Item | Specification |
| 1. Power supply | Three-phase 380 VAC -15% to +10%, 50/60 Hz ±5% |
| 2. Output voltage | DC 24 V, max 30 mA; short-circuit protected for DI/DO signals |
| 3. Motor control | Three-phase inverter |
| 4. Duty mode | S4-25%-1,200 starts/hour |
| 5. Modulating torque | 50% of maximum stall torque |
| 6. Ingress protection | IP67 |
| 7. Humidity | below 95% |
| 8. Ambient temperature | -25 to +60℃ |
| 9. Mounting position | any position |
| 10. Housing coating | Epoxy enamel coating (RAL 9005 black); exposed screws stainless steel (chromed drain plug) |
| 11. EMC immunity | Per EMC product standard EN 61800 part 3 |
| 12. EMC emission | Per EMC product standard EN 61800 part 3 |
| 13. Seismic capability | 0.75 g over 5–200 Hz or 2 g over 5–150 Hz, sinusoidal |
| 14. Analogue input | 4–20 mA, galvanically isolated, 250 Ω |
| 15. Digital input | Configurable isolated passive optocouplers: logic 0 -3 to +5 V; logic 1 12–35 V; min pulse width 50 ms |
| 16. Analogue output | Position 4–20 mA, max load 750 Ω, isolated, short-circuit protected, rising or falling characteristic, temperature effect ≤0.1%/10 K |
| 17. Digital output contacts | Standard 4 pairs of passive gold-plated relay contacts, expandable by 3 or 4 pairs, isolated, freely configurable, max 50 V, overload protected |