Among "uncommanded movement" faults, AUMA motor-operated valves feature prominently. This article merges two popular AUMA threads (21 and 15 replies): one where the valve closes by itself yet tests perfectly on site, and one where everything works except the automatic-close function. Together they form a complete troubleshooting framework for uncommanded motion.
Symptom: an AUMA MOV (controller AM 01.1) closes by itself during operation; on arrival, remote and local operation both behave — the fault will not reproduce.
Directions from the replies, by likelihood:
1. An automatic-close clause in the DCS logic — the most common cause: once the SCS condition is met the DCS commands the closure; the actuator itself is faultless
2. Command cabling: insulation breakdown, shorted or grounded command wires, water ingress — one engineer complains of construction-era cables "with joints wrapped in adhesive tape"; test the command cable insulation with a megger
3. Stuck interposing relays / solid-state relays (SSR): SSR sticking is an industry classic — one plant swapped contactors for SSRs and slept better, another fitted cheap SSRs and replaced them constantly; note that miniature DC-controlled SSRs are polarized — reversed wiring conducts outright (an engineer was "stunned" by this)
4. DCS cards: one brand's DO card is known to "fire commands erratically" when failing
5. Operator error: check the operation log
6. Cross-brand hint: EMG MOVs have closed themselves when hot air leaking from the stem overheated the control board into thermal protection — overheat protection also "moves things by itself"
Symptom: a high-pressure-heater drain valve (AUMA — opens automatically on steam extraction, closes automatically above 20% load) would not close automatically, though single-point and local control worked. Replacing the interface card (Z 027 072/01, 48VDC) fixed it — yet the removed card still works on other valves.
The question: why does single-point control work while automatic close does not — does the card use different detection elements for the two signals?
The analysis:
For uncommanded-motion troubles walk the three layers — logic → relays & cabling → actuator interface card: first DCS logic and DO historical trends (no dismantling needed), then megger the cables and swap interposing relays, and only then touch the actuator side, using the terminal-short-circuit test to draw the line. Complements our general framework article on self-operating valves.