EN  中

Electric Actuator Opens by Itself with No Command? How One Power Plant Traced the Root Cause in Over a Month

source:    date:2026-09-26

At a power plant, the large bypass electric actuator (a SIPOS 5 Flash ECOTRON, the economy-type unit of the SIPOS 5 Flash series) on the condensate polishing system of Unit 3 kept doing something strange in the spring of 2010: the valve opened by itself, although no one had issued an open command. It happened repeatedly over two weeks, at seemingly random moments, and the instrumentation & control (I&C) crew never managed to witness an event in person despite standing watch. With the plant in the middle of a critical power-supply guarantee period, this phantom fault became a top-priority investigation.

Symptoms

The maintenance team went through the field conditions and found five odd points:

1. Operators had never issued an open command, and there was no open-command record in the DCS;

2. A check of the PLC sequence logic confirmed that no interlock condition existed that would open the large bypass;

3. Repeated remote and local operation of the actuator worked perfectly in both directions;

4. The unwanted openings occurred at random, and the energization of the relay (24 V DC) lasted only about one second — nearly impossible to catch even when someone was standing right there;

5. After each unwanted opening, a close command from the DCS closed the valve normally, and everything behaved as usual.

In other words, the actuator looked "healthy" — yet it moved on its own, with no one commanding it.

The crew's initial analysis

The crew first ruled through the most obvious directions:

- Spurious relay pickup? Unlikely — the open-command relay was a 24 V DC type with strong interference immunity, wired to a normally-open contact that only picks up when energized;

- Broken conductor or short circuit in the circuit? Unlikely — remote operation was normal, which showed the loop was intact;

- Electromagnetic interference causing the actuator to misoperate? This was what the crew considered most probable, yet even the manufacturer did not think it likely.

With all three paths half-open and half-blocked, the team shared the symptoms and their analysis with peers in the field, and the troubleshooting directions that came back were highly representative.

Troubleshooting directions from peers

Direction 1: damaged control cables and damp intermediate joints causing shorts. This turned out to be the most frequent cause among similar cases. Several plants reported almost identical experiences: at one plant, multiple Yangxiu actuators repeatedly opened and closed by themselves with no DCS command; a site check revealed damaged outer sheaths on the actuator control cables, which shorted whenever they got damp — after the cables were repaired, the fault never returned. At another plant a Rotork actuator "opened by itself every time it rained," again traced to a damaged control cable. A third plant's pulverizer-exhaust hot-air damper misoperated because of a poorly routed cable joint that shorted. The advice was concrete: megger the control cable insulation, ask the electrical crew to run a withstand-voltage test to locate sheath damage, and pay special attention to intermediate cable joints — where shields and insulation are often poorly finished, allowing interference voltages into the loop. One I&C engineer reported measuring a 100 V interference voltage on a cable whose shield was intact. If the fault could not be located, laying a temporary new cable in parallel and observing for a period cleanly separates internal from external causes.

Direction 2: the actuator's own boards. Some peers suggested simply swapping in another actuator and letting the problem "reveal itself": if the fault disappeared after replacement, the original actuator was to blame; if it persisted, the cause was external. Board-level examples abounded: at one plant a SIPOS unit hunted when placed in automatic; no cause could be found until the boards were replaced one by one — after the control board and power supply board were changed, the symptom vanished. Elsewhere a control valve closed fully by itself because a relay contact had welded, feeding power to close the motor; replacing the relay cured it. Multiple reports pointed at power supply boards — "after a capacitor burns out, the board starts behaving insanely" — especially in hot locations, where power boards fail readily while control boards almost never do.

Direction 3: interference and grounding. Check whether the analog input lines are shielded cable and whether the shield is solidly single-point grounded; where possible, measure whether an AC component is superimposed on the PLC output channel — if so, interference becomes the prime suspect.

Interim measures: before the cause was found, the plant handled it pragmatically during the guarantee period — operate locally when needed, then switch off power afterward to prevent another unwanted stroke.

Diagram: parameter recovery lag after momentary power outage

Fig.1 After the momentary outage, analog parameters lag behind digital ones; the PLC misjudges within the window and issues the interlock-open command (diagram by this site)

More than a month later, the root cause

Nobody had guessed it: the real cause lay neither in the actuator nor in the cables, but in the combination of power-supply quality and sequence logic.

The PLC cabinet's main power supply dropped out momentarily. During the instant outage all monitored parameters disappeared; after the supply recovered, the parameters came back one by one — but the analog quantities recovered nearly 2 seconds slower than the digital ones (verified by experiment at the plant). So after every momentary outage, the PLC sequence judged that "analog monitoring was abnormal — the system was not running properly," and immediately opened the large bypass by interlock, exactly as programmed.

With the answer on the table, everything fit: no operator had issued the command — the sequence logic itself had; the finding that "no interlock condition could occur" had also been correct — under normal conditions it truly could not, and the abnormal trigger was that brief power dip. Remote operation, naturally, was flawless. The actuator had been innocent all along: it had merely executed a command whose origin no one understood at the time.

Corrective action and outcome

The plant's fix: feed a second power source into the main supply, providing dual-power supply. The system has run normally ever since, with no recurrence. Peers in the discussion reached a consensus as well: PLC sequence cabinets should be equipped with a UPS or dual supplies — and note that a UPS itself can drop out, so redundant supplies are the dependable practice.

Lessons from the case

When an electric actuator "moves by itself with no command," work through the following order:

1. Separate the three suspects first: where the command came from (DCS/PLC event records), the actuator itself, and the external circuit (cables/relays) — isolate them one by one;

2. Control cables are the most frequent culprit: sheath damage, intermediate joints, and damp-induced shorts dominate such cases — megger the insulation, inspect joints, and substitute a new cable if necessary;

3. Use component swapping to isolate board faults: power supply boards (capacitors in particular), control boards, and welded relay contacts — replace board by board, or swap the whole actuator, and internal vs. external causes become obvious;

4. Do not overlook power quality and sequence logic: momentary supply outages, the recovery-time difference between analog and digital parameters, and interlock conditions can all make an innocent actuator take the blame;

5. During critical guarantee periods, take interim measures first: operate locally and de-energize afterward until the cause is found.

 
    
Support:Shandong Juxi Electromechanical Equipment Co.,Ltd.    Tel:+86-13853147838     Email:actuators@163.com    WhatsApp:13853147838/18678894019
© 2006-2026 China Electric Actuator Network